Demonstration data. Metro Distribution Center is a fictional business.
- Compliance score
- 78%
- Compliant
- 78
- Not compliant
- 22
- Items checked
- 100
Of the 100 items that applied, 78 were compliant and 22 were not.
- Site
- Metro Distribution Center125,000 sq ft warehouse
- Inspected by
- Critical Dynamics Risk ManagementCredentials held on our team: CSP, CHMM, CSHM and RIMS-CRMP
- Checklists used
- NFPA 10 - Portable Fire Extinguishers
- Emergency Egress and Exit Routes
- Forklift and Powered Industrial Truck Safety
- Photos
- 25Every item to correct has at least one.
Items to correct (22)
3 critical, 7 high, 9 medium and 3 low. Due dates count from the day of the audit. In the client portal this list is the corrective action register.
Critical (3)
Fix within 24 hours
Critical
Emergency exit blocked by palletized inventory
- What the inspector found
- Four pallets of outbound stock were staged against the shipping dock exit. The door could not be opened from the inside.
- Recommended action
- Move the pallets and keep the route to the door clear. Mark the floor in front of the door as a no-storage zone and add the exit to the opening check for each shift.
Critical
Forklift #3 running with a failed parking brake
- What the inspector found
- With the parking brake set, forklift #3 rolled back on the dock ramp. The truck was in use during the audit.
- Recommended action
- Take forklift #3 out of service and tag it. Have an authorized technician repair and test the brake before the truck is used again.
Critical
Extinguisher #7 is 14 months past its last service
- What the inspector found
- The service tag on extinguisher #7 shows its last annual maintenance 14 months ago. Annual maintenance is due every 12 months.
- Recommended action
- Have a qualified extinguisher service company do the annual maintenance and tag the unit. Hang a serviced spare in its place until it is back.
High (7)
Fix within 7 days
- High
Extinguisher #4 blocked by stacked cartons
- What the inspector found
- Cartons stacked on the floor in front of extinguisher #4 left about 2 feet of clear space. The unit could not be reached without moving stock.
- Recommended action
- Clear the floor in front of the unit. Mark a keep-clear box on the floor so stock is not set there again.
- High
Extinguisher #11 gauge reads below the operable range
- What the inspector found
- The pressure gauge needle on extinguisher #11 sits to the left of the green band.
- Recommended action
- Swap the unit for a charged spare. Send #11 for recharge and have the technician look for the cause of the pressure loss.
- High
Three emergency lights failed the 30-second test
- What the inspector found
- Three of the 24 emergency light units did not come on when the test button was held for 30 seconds.
- Recommended action
- Replace the batteries or the units. Then test all 24 and record the result.
- High
Hydraulic fluid leaking from forklift #2
- What the inspector found
- A slow drip at the lift cylinder of forklift #2 left fluid on the floor of the receiving aisle.
- Recommended action
- Take the truck out of service until the cylinder seal is repaired. Clean the floor where it has been working.
- High
Forklift #5 left unattended with the forks raised
- What the inspector found
- Forklift #5 was parked in aisle 12 with the forks about 3 feet off the floor and the key switched on. No operator was in sight.
- Recommended action
- Lower the forks, neutralize the controls, shut off the power and set the brake every time a truck is left. Go over the rule with every operator at the next shift meeting.
- High
Two forklift operators are overdue for evaluation
- What the inspector found
- Training records show two of the eight operators were last evaluated more than three years ago.
- Recommended action
- Evaluate both operators on the trucks they drive and certify the result. Keep them off the trucks until that is done.
- High
Tamper seal missing on extinguisher #5
- What the inspector found
- The pull pin on extinguisher #5 is in place but its tamper seal is gone.
- Recommended action
- Check the gauge and the weight of the unit, then fit a new seal.
Medium (9)
Fix within 30 days
- Medium
Three extinguishers show no monthly check for two months
- What the inspector found
- The tags on extinguishers #2, #6 and #9 have no initials for the last two months.
- Recommended action
- Check every extinguisher each month and initial its tag. Assign the round to one position on each shift.
- Medium
No extinguisher education on record in the past year
- What the inspector found
- The last recorded fire extinguisher education for warehouse staff was more than 12 months ago. Six employees hired since then have none on record.
- Recommended action
- Give the education to every employee expected to use an extinguisher, repeat it each year and keep the sign-in sheet.
- Medium
Extinguisher #8 standing on the floor
- What the inspector found
- Extinguisher #8 was standing on the floor beside its empty wall bracket.
- Recommended action
- Hang the unit on its bracket. Replace the bracket strap if it no longer holds.
- Medium
Two exit signs are not lit
- What the inspector found
- The exit signs over doors B2 and B3 were dark.
- Recommended action
- Replace the lamps or the sign units. Add both signs to the monthly emergency lighting test.
- Medium
Emergency lighting tests not recorded for four months
- What the inspector found
- The emergency lighting log shows its last monthly test four months ago.
- Recommended action
- Test every unit for 30 seconds each month and for 90 minutes once a year. Record both.
- Medium
Daily forklift examinations missing for two days
- What the inspector found
- The pre-shift checklist binder has no entries for two of the last ten working days. Operators on shift could not say whether the trucks were examined on those days.
- Recommended action
- Examine every truck before each shift and record it. Have the shift lead confirm the checklist before a truck goes into service.
- Medium
No marked walkway through the shipping area
- What the inspector found
- People on foot and forklifts share the main shipping aisle. The aisle has no marked walkway, and the dock office door opens straight into it.
- Recommended action
- Mark a walkway from the dock office along the wall and keep forklifts out of it. Put a barrier rail where the office door opens into the aisle.
- Medium
Capacity plate on forklift #5 cannot be read
- What the inspector found
- The capacity plate on forklift #5 is worn. The rated capacity and the load center cannot be read.
- Recommended action
- Get a replacement plate from the manufacturer and fit it. Check that the plate matches the attachments on the truck.
- Medium
Charging station has nothing to flush or neutralize battery acid
- What the inspector found
- Batteries are watered and charged at the station by dock door 1. There is no eyewash and no neutralizer for spilled electrolyte.
- Recommended action
- Install an eyewash at the station and stock a neutralizer for spilled electrolyte. Show each operator where they are.
Low (3)
Fix within 90 days
- Low
Extinguisher #12 cannot be seen from the aisle
- What the inspector found
- Extinguisher #12 hangs on a column behind an end-of-aisle rack. It cannot be seen from the main aisle and there is no sign above the rack.
- Recommended action
- Mount a sign high on the column so the location can be seen from the aisle.
- Low
Storage room door beside the dock exit has no sign
- What the inspector found
- The door to the pallet storage room is next to the shipping dock exit and carries no sign. It could be mistaken for the way out.
- Recommended action
- Post a "Not an Exit" sign on the door, or a sign that names the room.
- Low
No "No smoking" sign at the battery charging station
- What the inspector found
- The charging station has no sign that prohibits smoking. Nobody was seen smoking there during the audit.
- Recommended action
- Post a no smoking sign at the station and go over the rule at the next shift meeting.
Checklist results
| Item | Reference | Result | Notes |
|---|---|---|---|
| NFPA 10 - Portable Fire ExtinguishersChecklist 1 of 3 | |||
| Is an extinguisher within 75 feet of travel in every area? | OSHA 1910.157(d)(2) (opens the regulation in a new tab) | Compliant | Longest travel measured: 48 ft |
| Is each extinguisher easy to reach and not blocked? | OSHA 1910.157(c)(1) (opens the regulation in a new tab) | Not compliant | #4 blocked by stacked cartons |
| Does each extinguisher show annual maintenance in the last 12 months? | NFPA 10 | Not compliant | #7 last serviced 14 months ago |
| Is each cylinder free of dents, cracks and damage? | NFPA 10 | Compliant | All 12 units checked |
| Emergency Egress and Exit RoutesChecklist 2 of 3 | |||
| Are all exit doors unlocked and free of devices that prevent egress? | OSHA 1910.36(d)(1) (opens the regulation in a new tab) | Compliant | All 6 doors verified |
| Are exit routes free from obstructions? | OSHA 1910.37(a)(3) (opens the regulation in a new tab) | Not compliant | Dock exit, 4 pallets |
| Do exit routes keep the required clear width? | OSHA 1910.36(g)(2) (opens the regulation in a new tab) | Compliant | 44 in. or more |
| Are all exit signs lit? | OSHA 1910.37(b)(6) (opens the regulation in a new tab) | Not compliant | 2 signs dark in zone B |
| Forklift and Powered Industrial Truck SafetyChecklist 3 of 3 | |||
| Is every truck examined before each shift? | OSHA 1910.178(q)(7) (opens the regulation in a new tab) | Not compliant | No entries for 2 of the last 10 working days |
| Does the parking brake hold the truck on an incline? | OSHA 1910.178(q)(1) (opens the regulation in a new tab) | Not compliant | #3 rolled back on the dock ramp |
| Is the overhead guard on each truck in place and undamaged? | OSHA 1910.178(e)(1) (opens the regulation in a new tab) | Compliant | All 5 trucks checked |
| Are loads kept within the rated capacity of the truck? | OSHA 1910.178(o)(2) (opens the regulation in a new tab) | Compliant | Observed on three trucks |
12 of the 100 items are shown here. The full report lists every item the same way.
Inspector notes
We walked warehouse zones A through D, both docks, the battery charging station and the offices, and reviewed the training and maintenance records kept on site.
Forklift #3 was tagged out of service before we left. The pallets at the shipping dock exit were moved while we were on site. Without a marked no-storage zone in front of that door, the same thing is likely to happen again.
Most of the medium and low items are upkeep: monthly checks, lighting tests and records. Two items, forklift operator evaluations and fire extinguisher education, need a date on the training calendar.