Demonstration Report Only

This is a sample inspection report created for demonstration purposes only. All information contained within this document is entirely fictional and simulated for illustrative purposes.

"Metro Distribution Center" is a fictional business. All names, locations, findings, and safety concerns are fabricated examples designed to demonstrate the comprehensive nature of Critical Dynamics Risk Management's inspection services. No real persons, businesses, or actual hazards are represented in this report.

Client Privacy Commitment: Critical Dynamics Risk Management maintains strict confidentiality of all actual client information. Real inspection reports and client data are never used for marketing or demonstration purposes. We are committed to protecting the privacy and security of all our clients' information.

Critical Dynamics Risk Management
Professional Risk Assessment & Compliance
Report #: WHS-2025-1142
Date: November 28, 2025

Safety & Compliance Inspection Report

CLIENT INFORMATION
Business Name
Metro Distribution Center
Location
8500 Industrial Parkway, Houston, TX 77041
Contact Person
Robert Martinez, Operations Manager
Phone
(713) 555-0847
Business Type
Warehouse & Distribution
Square Footage
125,000 sq ft
INSPECTION DETAILS
Inspection Date
November 27, 2025
Inspection Time
8:00 AM - 2:30 PM
Inspector Name
Jennifer Walsh, CSP
Certification #
CSP-2021-5893
Inspection Type
Comprehensive Multi-Module Safety Audit
Modules Inspected
NFPA 10, Emergency Egress, Forklift Safety
EXECUTIVE SUMMARY
3
Critical
6
High
9
Medium
4
Low
78
Overall Compliance Score
NFPA 10 - Fire Extinguishers
38 Pass
8 Fail
6 N/A
Emergency Egress & Exit Routes
22 Pass
5 Fail
3 N/A
Forklift & Industrial Truck Safety
26 Pass
9 Fail
3 N/A

Immediate Action Required

Three critical safety issues were identified requiring immediate correction: (1) Fire extinguisher #7 in Warehouse Zone C has expired annual service - last serviced 14 months ago per NFPA 10-7.4.3, (2) Emergency exit in Shipping Dock area blocked by palletized inventory preventing egress per OSHA 1910.37(a)(3), and (3) Forklift #3 operating with failed parking brake per OSHA 1910.178(q)(1). These items must be addressed within 24 hours.

INSPECTION CHECKLIST RESULTS
NFPA 10 - Portable Fire Extinguishers (52 Questions)

Reference: NFPA 10: Standard for Portable Fire Extinguishers, 2022 Edition

ID Category Inspection Question Response Notes
NFPA10-001 Location & Accessibility Is the fire extinguisher mounted in its designated location per floor plan/records? YES All 12 units verified
NFPA10-002 Location & Accessibility Is the extinguisher mounted at the correct height (top not more than 5 feet for 40 lbs or less)? YES Heights measured and compliant
NFPA10-003 Location & Accessibility Is the extinguisher easily accessible and not blocked by equipment, materials, or debris? NO Unit #4 blocked by pallet rack overflow - 2ft clearance only
NFPA10-008 Location & Accessibility Is the travel distance to this extinguisher within maximum limits (75 ft for Class A, 50 ft for Class B)? YES All zones measured - max 48ft travel
NFPA10-009 Cylinder Inspection Is the cylinder free from dents, cracks, or physical damage? YES All cylinders inspected
NFPA10-010 Cylinder Inspection Is the cylinder free from corrosion or rust? NO Unit #9 shows surface rust on bottom rim
NFPA10-013 Pressure Gauge Is the pressure gauge needle in the green (operable) range? NO Unit #11 gauge reading in yellow zone - needs recharge
NFPA10-019 Inspection Tag Is a monthly inspection tag/card attached showing current month initial? NO 3 units missing October/November initials
NFPA10-020 Inspection Tag Is an annual maintenance tag present showing service within last 12 months? NO CRITICAL: Unit #7 last service 14 months ago
NFPA10-024 Tamper Seal Is a tamper seal or indicator present and intact? YES All seals verified intact
NFPA10-028 Discharge Mechanism Is the discharge nozzle or horn securely attached and unobstructed? YES All nozzles clear
NFPA10-031 Agent Type Is the extinguishing agent type appropriate for the hazards in this area? YES ABC units appropriate for mixed hazards
NFPA10-038 Type-Specific: Dry Chemical For dry chemical extinguishers: Does powder appear free-flowing when shaken? NO Unit #2 powder sounds caked when shaken
NFPA10-040 Type-Specific: Class K For Class K extinguishers: Is unit located within 30 feet of kitchen cooking equipment? N/A No commercial kitchen present
NFPA10-052 Overall Assessment Based on overall inspection, is this extinguisher in serviceable condition and ready for emergency use? NO 3 units require immediate service

* Showing representative sample of checklist items. Full inspection covered all 52 questions per NFPA 10 module.

Emergency Egress and Exit Routes (30 Questions)

Reference: NFPA 101 Life Safety Code and OSHA 1910 Subpart E - Means of Egress

ID Category Inspection Question Response Notes
EGRESS-001 Exit Doors Are all exit doors unlocked and free from devices that prevent immediate egress? YES All 6 exit doors verified
EGRESS-002 Exit Doors Do all exit doors swing in the direction of egress travel (outward for high occupancy)? YES All doors swing outward
EGRESS-003 Exit Doors Are all exit doors in good operating condition and able to open fully? NO East exit door sticks - closer adjustment needed
EGRESS-005 Exit Routes Are all exit routes and paths of egress free from obstructions? NO CRITICAL: Shipping dock exit blocked by 4 pallets
EGRESS-006 Exit Routes Do exit routes maintain minimum required width (typically 28-44 inches clear)? YES All corridors 44"+ width maintained
EGRESS-008 Exit Signs Are illuminated exit signs present at all required locations? YES All 14 exit signs present
EGRESS-009 Exit Signs Are all exit signs properly illuminated? NO 2 exit signs have burned out bulbs - warehouse zone B
EGRESS-012 Emergency Lighting Is emergency lighting installed in all exit routes and exit access? YES 24 emergency light units installed
EGRESS-013 Emergency Lighting Are all emergency light units functional with charged batteries? NO 3 units failed 30-second test - batteries dead
EGRESS-014 Emergency Lighting Are emergency lights tested monthly with results documented? NO Last documented test was 4 months ago
EGRESS-015 Stairways Are all exit stairways readily accessible and not locked from the egress side? N/A Single-story facility
EGRESS-022 Fire Doors Do all fire-rated doors self-close and latch properly? YES All fire doors tested - functioning properly
EGRESS-025 Evacuation Plans Are emergency evacuation plans posted in visible locations? YES Plans posted at all 6 locations
EGRESS-029 Evacuation Training Are fire drills conducted regularly (annually minimum)? YES Last drill 3/15/2025 - documented
EGRESS-030 Overall Assessment Based on overall inspection, are life safety and egress systems adequate for safe evacuation? YES With noted corrections, systems adequate

* Showing representative sample of checklist items. Full inspection covered all 30 questions per Emergency Egress module.

Forklift and Powered Industrial Truck Safety (38 Questions)

Reference: OSHA 1910.178 - Powered Industrial Trucks

ID Category Inspection Question Response Notes
FORK-001 Pre-Op Inspection Are all forklifts inspected daily before each shift per the operator checklist? NO Missing inspections for 11/22 and 11/25
FORK-002 Visual - Forks Are forks free from cracks, damage, and excessive wear? YES All 5 units inspected - forks good condition
FORK-004 Hydraulic System Is hydraulic fluid at proper level without visible leaks? NO Unit #2 showing slow drip at lift cylinder
FORK-006 Mast & Carriage Does mast operate smoothly in both lift and tilt functions without binding? YES All units tested
FORK-007 Mast & Carriage Are mast chains properly tensioned and lubricated without kinks or broken links? NO Unit #4 chains dry - needs lubrication
FORK-008 Overhead Guard Is overhead guard in good condition without damage or missing components? YES All guards intact
FORK-011 Brakes Do service brakes function properly and bring forklift to controlled stop? YES All service brakes tested satisfactory
FORK-012 Brakes Does parking brake hold forklift stationary on inclines? NO CRITICAL: Unit #3 parking brake slips on ramp
FORK-015 Safety Equipment Is audible warning device (horn) functioning properly? YES All horns operational
FORK-017 Safety Equipment Is seatbelt present, in good condition, and functioning? NO Unit #1 seatbelt retractor not working
FORK-023 Labels & Data Plates Are capacity plate and safety labels present and legible? NO Unit #5 capacity plate faded - barely legible
FORK-024 Operator Requirements Are all forklift operators properly trained and certified per OSHA requirements? YES All 8 operators certified - records verified
FORK-027 Load Handling Are loads being handled within the rated capacity of the forklift? YES Observed operations within capacity
FORK-030 Traffic Safety Are traffic lanes, aisle markings, and clearances properly maintained? NO Aisle markings faded in zones A and C
FORK-031 Pedestrian Safety Are pedestrians properly separated from forklift traffic? NO No designated pedestrian walkway in shipping area
FORK-037 Maintenance Are unsafe forklifts immediately tagged out of service? YES LOTO procedures in place
FORK-038 Overall Assessment Based on overall inspection, is the forklift safety program effectively implemented? NO Program needs improvement in daily inspections and maintenance

* Showing representative sample of checklist items. Full inspection covered all 38 questions per Forklift Safety module.

DETAILED FINDINGS SUMMARY
Item # Module/Code Finding Severity Deadline
001 NFPA10-020 Fire extinguisher #7 (Warehouse Zone C) annual service overdue - last serviced 14 months ago Critical 24 Hours
002 EGRESS-005 Emergency exit in Shipping Dock blocked by 4 pallets of inventory, preventing egress Critical Immediate
003 FORK-012 Forklift #3 parking brake fails to hold on loading dock ramp - slips under load Critical Immediate
004 NFPA10-003 Fire extinguisher #4 blocked by pallet rack overflow - only 2ft clearance (requires 3ft) High 48 Hours
005 NFPA10-013 Fire extinguisher #11 pressure gauge in yellow zone indicating undercharge High 7 Days
006 EGRESS-013 3 emergency light units failed 30-second test - batteries require replacement High 7 Days
007 FORK-004 Forklift #2 hydraulic system showing slow drip at lift cylinder seal High 7 Days
008 FORK-017 Forklift #1 seatbelt retractor mechanism not functioning - belt does not retract High 48 Hours
009 FORK-031 No designated pedestrian walkway in shipping area - pedestrians mixing with forklift traffic High 14 Days
010 NFPA10-010 Fire extinguisher #9 showing surface rust on bottom rim - monitor for progression Medium 30 Days
011 NFPA10-019 3 fire extinguishers missing October/November monthly inspection initials Medium 7 Days
012 NFPA10-038 Fire extinguisher #2 dry chemical powder appears caked when shaken Medium 14 Days
013 EGRESS-003 East exit door sticks when opening - door closer requires adjustment Medium 14 Days
014 EGRESS-009 2 exit signs in Warehouse Zone B have burned out illumination bulbs Medium 7 Days
015 EGRESS-014 Emergency lighting monthly testing not documented - last test 4 months ago Medium 7 Days
016 FORK-001 Daily pre-shift forklift inspections missing for 11/22 and 11/25 Medium Ongoing
017 FORK-007 Forklift #4 mast chains dry - requires lubrication per maintenance schedule Medium 7 Days
018 FORK-030 Aisle markings faded in warehouse zones A and C - traffic lanes difficult to identify Medium 30 Days
019 FORK-023 Forklift #5 capacity plate faded and barely legible - replacement needed Low 30 Days
020 NFPA10-005 Fire extinguisher location sign at Unit #6 partially obscured by equipment Low 30 Days
021 EGRESS-011 Directional exit sign arrow at corridor junction faded - needs replacement Low 60 Days
022 FORK-022 Forklift #2 hour meter display dim - difficult to read Low 60 Days
PHOTOGRAPHIC DOCUMENTATION

Client Privacy Protection Notice

Actual inspection reports include detailed photographic evidence of all findings captured via the mobile inspection app. For this demonstration report, placeholder images are shown to protect client confidentiality. In production reports, high-resolution photographs document each safety concern with timestamps, GPS coordinates, and direct links to checklist items.

Critical Findings - Immediate Action Required

Photo Evidence
Protected
Finding #001 - Fire Extinguisher Annual Service Overdue
Extinguisher #7 service tag showing last annual maintenance 14 months ago
NFPA 10 - 7.4.3
Photo Evidence
Protected
Finding #002 - Blocked Emergency Exit
Shipping dock exit blocked by palletized inventory preventing egress
OSHA 1910.37(a)(3)
Photo Evidence
Protected
Finding #003 - Forklift Parking Brake Failure
Forklift #3 on loading dock ramp demonstrating parking brake slip
OSHA 1910.178(q)(1)

High Priority Findings

Photo Evidence
Protected
Finding #004 - Fire Extinguisher Access Blocked
Extinguisher #4 with only 2ft clearance due to pallet rack overflow
NFPA 10 - 6.1.5.1
Photo Evidence
Protected
Finding #006 - Emergency Light Battery Failure
Emergency light unit failing 30-second illumination test
OSHA 1910.37(b)(4)
Photo Evidence
Protected
Finding #007 - Hydraulic System Leak
Forklift #2 lift cylinder showing hydraulic fluid drip
OSHA 1910.178(q)(7)
Photo Evidence
Protected
Finding #009 - Pedestrian/Forklift Mixing
Shipping area showing lack of designated pedestrian walkway
OSHA 1910.178(n)(4)
REGULATORY COMPLIANCE STATUS
NFPA 10 Fire Extinguishers
Partial Compliance
NFPA 101 Life Safety Code
Partial Compliance
OSHA 1910.37 Egress
Non-Compliant
OSHA 1910.178 Forklifts
Non-Compliant
Emergency Action Plan
Compliant
Employee Training Records
Compliant
PRIORITY RECOMMENDATIONS

Immediate Actions (Within 24 Hours)

  • Clear shipping dock emergency exit - remove all pallets blocking egress path
  • Tag out Forklift #3 from service until parking brake is repaired and tested
  • Schedule certified fire extinguisher service for Unit #7 - annual maintenance overdue

High Priority (Within 7 Days)

  • Clear access to fire extinguisher #4 - maintain minimum 3ft clearance per NFPA 10
  • Recharge fire extinguisher #11 - pressure gauge indicating undercharge
  • Replace batteries in 3 failed emergency light units
  • Repair Forklift #2 hydraulic cylinder seal to stop leak
  • Replace Forklift #1 seatbelt retractor mechanism
  • Establish monthly emergency lighting test program with documentation
  • Update fire extinguisher monthly inspection tags (3 units)

Medium Priority (Within 30 Days)

  • Install designated pedestrian walkways in shipping area with floor markings
  • Refresh aisle markings in warehouse zones A and C
  • Service fire extinguisher #2 - dry chemical appears caked
  • Adjust east exit door closer to eliminate sticking
  • Replace burned out exit sign bulbs in Zone B
  • Lubricate mast chains on Forklift #4
  • Implement consistent daily pre-shift forklift inspection program

Long-term Improvements (30-60 Days)

  • Replace faded capacity plate on Forklift #5
  • Replace faded directional exit sign at corridor junction
  • Monitor fire extinguisher #9 for rust progression
  • Relocate fire extinguisher location sign at Unit #6 for better visibility
  • Consider digital maintenance tracking system for all safety equipment
FOLLOW-UP ACTIONS
Re-inspection Required
Yes - Critical items
Re-inspection Date
December 5, 2025
Next Full Audit
November 27, 2026
Quarterly Review
February 27, 2026